2 relt settings for bus differential, 3 relt settings for multi-source ground-fault – GE Industrial Solutions Entellisys 5.0 Administrator Manual User Manual

Page 31

Advertising
background image

Administration

31

5

5.3.2 RELT Settings for Bus Differential

Bus Diff will operate using Topology 0 settings while in Multi-point RELT or System Wide RELT.

The minimum settings for Bus Differential zones for both Alarm-Only and Trip Relays for
Topology 0 are:

NOTE: Although the Pickup is set to 100 Amps, Entellisys automatically enforces a “Zone
Minimum Pickup Setting” for Bus Differential. The “Zone Minimum Pickup Setting” is 20% of the
largest CT rating in the corresponding zone.

5.3.3 RELT Settings for Multi-Source Ground-Fault

Multi-Source Ground-Fault will operate on Topology 0 settings while in Multi-point RELT or
System Wide RELT.

The minimum settings for Multi-Source Ground-Fault zones for both Alarm-Only and Trip
Relays for Topology 0 are:

Setting

Value

Pickup Setting 1 & Pickup Setting 2

100A

Time Delay 1 & Time Delay 2

BAND 1

Backup Function (For Trip Relay only)

Enabled

Backup Time Delta (For Trip Relay only)

Trip

Immediately

Setting

Value

Pickup Setting

30 Amps

Time Delay

BAND 1

Curve I

2

T

DISABLED

Backup Function (For Trip Relay only)

Trip

Immediately

Backup Time Delta (For Trip Relay only)

Trip

Immediately

Advertising