User administration
22
4
4.2.3.1 Setup
Navigate to the “Restricted Breaker Control” tab from the Main Menu, Maintenance screen -
administrative login is required.
Figure 4-6 Restricted Breaker Control Setting Screen
Open / Close and Trip Code Text Boxes
Enter the code that is required to operate the associated breaker(s) in restricted mode. The
default value for the Open/Close/Trip code is “2.” Allowable values are from 2 to 65535.
Breaker Operation Matrix
Check the operations per breaker which require restricted control.
NOTE: Restricting operations will prevent the HMI from sending said actions to the respective
breaker(s).