Configuring Lineups

51

8

Figure 8-2 HMI Preferences

To add a lineup
1.
Enter in the Lineup name (Must be unique and is limited to 30 characters)
2. Enter the Lineup Description (Limited to 250 characters)
3. Enter IP Addresses for both CPUA and CPUB (Must be unique)
4. Click the Startup Lineup to specify the default lineup
5. Click the “Add Lineup” button

To modify a lineup
1.
Click on the desired lineup in the list and the Name, Description and IP addresses will

populate with the lineup information - edit the information

2. Select “Update Lineup

To Delete a lineup
1.
Click on the desired lineup in the list and the Name, Description and IP addresses will

populate with the lineup information

2. Select “Delete Lineup” (The current lineup and startup lineup cannot be deleted)

The Startup Lineup
The Startup Lineup is the default lineup which the HMI connects to each time the Remote HMI
software is started

Configuration file upload

After either changing the default lineup or when connecting to an Entellisys Lineup for the first
time, the HMI will attempt to connect and upload all HMI files from the CPUs of the respective
lineup. (See figure

8-3

) If the CPUs are unavailable, the lineup will still be entered and HMI will try