5 ventilation and cooling – GE Industrial Solutions LP 33 Series 50 & 60 kVA Installation Guide User Manual

Page 19

Advertising
background image

Modifications reserved

Page 19/42

OPM_LPS_3UI_50K_60K_0US_V010.doc

Installation Guide LP 33 Series 50-60 kVA

3.5 VENTILATION

AND

COOLING


The heat produced by the UPS is transferred to the environment by its internal blowers.

Airflow through the UPS

It is important that the cooling air can freely flow
through the air inlets and outlets of the UPS.

Fig. 4.5-1 Airflow through the LP 33 Series

NOTE !

Do not put any object on the top of the
cabinet: it might obstruct the air flow.

Heat evacuation from UPS room

The heat must be evacuated from the
environment with a proper cooling /
ventilation system provided by the
user.

Fig. 4.5-2 Heat evacuation from UPS room



Air volume and losses of the UPS

The approximate minimum air volume needed to evacuate the heat generated by the UPS, for inlet
temperature max. 35°C
(95°F), for the standard version at inverter nominal load with PF = 0.9 lag. and
battery charged, are the following:

Losses

Cooling air flow

UPS model

VFI Mode

ECO Mode

VFI Mode

ECO Mode

LP 33 Series / 50 kVA

16690 BTU/hr

4.89 kW

3482 BTU/hr

1.02 kW

847 CFM

1440 m

3

/h

173 CFM

294 m

3

/h

LP 33 Series / 60 kVA

20478 BTU/hr

6.0 kW

4164 BTU/hr

1.22 kW

1040 CFM

1767 m

3

/h

211 CFM

359 m

3

/h