Installation Guide LP 33 Series 50-60 kVA

3.9.2

Dual input utility (option)

Fig. 3.9.2-1 Dual input utility (option)

Dual input utility

On request, the UPS can be delivered for dual input
utility
.

Two independent lines (F2 and F3) supply separately
the rectifier and the bypass inputs

With this configuration, when the rectifier-input fuses
are opened, the automatic bypass and the
maintenance bypass are supplied by the other line.


Fig. 3.9.2-2 Terminals for dual input utility

X1 Mains 1 - Rectifier input utility connection

L1-1 = Rectifier Phase A
L2-1 = Rectifier Phase B
L3-1 = Rectifier Phase C
N1 =

Mains

Neutral

PE =

Main

Ground

X2 Mains 2 - Bypass input utility connection

L1-2 = Bypass Phase A
L2-2 = Bypass Phase B
L3-2 = Bypass Phase C
N =

Mains

Neutral

X3 Load - Output load connection

L1 = Load

Phase

A

L2 = Load

Phase

B

L3 = Load

Phase

C

N2 =

Load

Neutral

GND = Load Ground

Connect wire to the terminals by using
appropriate tools and appropriate torque
.

Torque specification for Input / Output and DC
power connections on Terminals
: Section 3.8.1.

LP 33 Series / 50 kVA

350 MCM

Max. rating X1, X2 , X3 and X4 terminals:

LP 33 Series / 60 kVA

350 MCM

NOTE !

For UPS correct operation, the input utility phase rotation must be clock-wise.

Inside the UPS, all neutrals N1 and N2 are connected together.


NOTE !

This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.