2 relay card – GE Industrial Solutions LP 33 Series 50 & 60 kVA Installation Guide User Manual

Page 37

Advertising
background image

Modifications reserved

Page 37/42

OPM_LPS_3UI_50K_60K_0US_V010.doc

Installation Guide LP 33 Series 50-60 kVA

4.2 RELAY

CARD

WARNING !

Connections described in this chapter shall be done only by a trained person or
SERVICE ENGINEERS
.


The Relay Card, allows the programming of 4 output channels on dry contacts, which can be read on
either terminal J3 or plug J4 (sub - D - male 9 pin).

Default configuration:

1

2

3

General alarm (NO)

4

Utility failure (NC)

5 C

(common)

6

Load on utility (NO)

7 Stop

operation

8 C

(common)

9

Utility failure (NO)

NO = Normally Open C

= Common NC

= Normally Closed

Voltage free contacts:

Max.: 60VDC or 30VAC / 0.5A
Min. signal level: 5VDC / 5mA

Fig. 4.2-1 Relay Card

Output signals on voltage-free contacts

On terminals J3 or J4 connector 4 of the following 28 signals can be selected from the display
(access only with password): MENU / PARAMETER MENU / LEVEL 2: SERVICE.

0 - No signal

15 - Battery discharge

1 - Buzzer

16 - Manual bypass ON

2 - General alarm (NO)

17 - Rectifier ON

3 - Load on utility

18 - Inverter ON

4 - Stop operation

19 - Battery boostcharge

5 - Load on inverter

20 - Battery earth fault

6 - Utility failure

21 - Battery fault

7 - DC overvoltage

22 - Relay input 1

8 - Low battery

23 - Relay input 2

9 - Overload

24 - Relay output ON

10 - Overtemperature

25 - Relay output OFF

11 - Inverter utility not syncrony

26 - EPO (Emergency Power Off)

12 - Bypass locked

27 - ECO Mode ON

13 - Bypass utility failure

28 - General alarm (NC)

14 - Rectifier utility failure

NOTE !

The function GEN-ON is not available on the Relay Card.
In case this function is needed, the optional Customer Interface
card must be installed
(see Section 4.4.1)
.