Installation Guide LP 33 Series 50-60 kVA

3.9 ELECTRICAL

CONNECTIONS

WARNING !

The connections to and from the UPS must be executed by QUALIFIED PERSONNEL
ONLY.

Refer to the “Safety prescriptions - Installation” described on page 6.

3.9.1

Common input utility

Fig. 3.9.1-1 Common input utility

Common input utility

The UPS delivered in standard version has
common input utility.
Only one input line (F1) supplies both rectifier
and bypass input terminals.

Bear in mind that when the utility fuses are
opened there is a supply failure to the rectifier
as well as to the automatic bypass and manual
bypass.

Fig. 3.9.1-2 Terminals for common input mains

X1 Utility 1 - Input utility connection

L1 = Rectifier + Bypass Phase A
L2 = Rectifier + Bypass Phase B
L3 = Rectifier + Bypass Phase C
N1 = Utility

Neutral

GND = Main Ground

X3 Load - Output load connection

L1 = Load

Phase

L1

L2 = Load

Phase

L2

L3 = Load

Phase

L3

N2 = Load

Neutral GND = Load Ground

LP 33 Series / 50 kVA

350 MCM

Max. rating X1, X3 and X4 terminals:

LP 33 Series / 60 kVA

350 MCM

Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: Section 3.8.1.

NOTE !

For UPS correct operation, the input utility phase rotation must be clock-wise.

Inside the UPS, all neutrals N1 and N2 are connected together.

NOTE !

This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.