GE Industrial Solutions LP 33 Series 50 & 60 kVA Installation Guide User Manual

Page 34

Advertising
background image

Modifications reserved

Page 34/42

OPM_LPS_3UI_50K_60K_0US_V010.doc

Installation Guide LP 33 Series 50-60 kVA

Fig. 3.9.4-4 Control bus location RPA parallel system


Control bus location RPA parallel system

Place the cables and connect them as indicated in the diagram Fig. 3.9.5-4 following these
procedures:

x

Fix the control bus cables with the appropriate tie-wrapE”.

x

Place the cables between the parallel units in separated protected conduit to avoid they could
be accidentally interrupted.

x

Put in place the front screen B (Fig. 3.9.4-1) paying attention to not damaging the control bus
cables.



It is important to place the units in sequence of their assigned number.

A unit number from P1 to P4, is defined by the setting of parameters and displayed on the control
panel
.
This number is also marked inside and outside the packaging.


The standard length of the control bus cable between two parallel unit is 26 ft / 8 m.