4 CUSTOMER INTERFACE

4.1 CUSTOMER INTERFACE

Serial port J3 - RS 232 (sub D - female 9 pin)

Modifications reserved

Page 41/45

OPM_SGS_ISG_10K_40K_0US_V040.doc

Installation Guide SG Series 10 –20 – 30 - 40 kVA

Suitable for JUMP protocol

Pin 2: TX (out)

Pin 3: RX (in)

Pin 5: GND

J2 (subD-female 25p) – Output signals on voltage free contacts

J2/1, 2, 3

NO, C, NC

Utility Failure

(default Parameter RL=1)

J2/4, 5, 6

NO, C, NC

Load on Inverter (default Parameter RL=3)

J2/7, 8, 9

NO, C, NC

Stop Operation

(default Parameter RL=5)

J2/14, 15, 16

NO, C, NC

Load on Utility

(default Parameter RL=2)

J2/17, 18, 19

NO, C, NC

General Alarm

(default Parameter RL=4)

J2/20, 21, 22

NO, C, NC

Acoustic Alarm

(default Parameter RL=6)

Signals on terminals X1 and on connector J2 are in parallel and

therefore not separated galvanically from each other.

The programmable signals on X1 and J2 will be disabled with Q1 open, with

the exception of the signals for “16 - Manual Bypass ON” and “26 - EPO”.

XB - Terminals for EPO connection

XB/1, 4 or J2/12, 25

NC

EPO (Emergency Power Off)

See Section 4.1.7

Note: to enable this function, remove cable short-circuiting XB / 2 – 3 and

the Jumper JP3 on P4 – Customer Interface.

X1 – Output signals on voltage free contacts - terminals

X1/1, 2, 3

NO, C, NC

Utility Failure

(default Parameter RL=1)

X1/4, 5, 6

NO, C, NC

Load on Inverter (default Parameter RL=3)

X1/7, 8, 9

NO, C, NC

Stop Operation

(default Parameter RL=5)

X1/12, 13, 14

NO, C, NC

Load on Utility

(default Parameter RL=2)

X1/15, 16, 17

NO, C, NC

General Alarm

(default Parameter RL=4)

X1/18, 19, 20

NO, C, NC

Acoustic Alarm

(default Parameter RL=6)

Input contacts

X1/10, 21 or J2/10, 23

Programmable (default = RL1)

X1/11, 22 or J2/11, 24

Programmable / Generator ON (NO) (def. = RL2)

1

12

1

3

2

14

3

15

4

16

5

17

6

18

7

19

8

20

9

21

10

22

11

1

14

9

1

X1

J2

J3

S

G

T5000_100

-150_

C

u

s

tomer in

ter

fa

c

e_

0

1

J5

J4

XA

2

1

XB

1

2

3

4

1

2

3

4

JP3

Fig. 4.1-1 Customer interface

NO = Normally Open

C = Common

NC = Normally Closed

The connectors J4 and J5 can be used for additional Advanced SNMP Card or an additional Customer Interface
(installation only when the UPS is switched Off).
XA: terminals for 24VDC Auxiliary Power Supply connection.

XB: terminals for EPO connection.

Programmable user relays

Programmable functions on contacts (X1 - J2)

On terminals X1 or J2 connector, six of the following 26
signals
can be selected from the display, entering with
the appropriate password.

0- No Information
1- Buzzer
2- General Alarm
3- Load on Utility
4- Stop Operation
5- Load on Inverter
6- Utility Failure
7- DC Over Voltage
8- Low Battery
9- Overload
10- Over Temperature
11- Inverter-Utility not syncr.
12- Bypass Locked
13- Bypass Utility Failure

14- Rectifier Utility Failure
15- Battery Discharge
16- Manual Bypass ON
17- Rectifier ON
18- Inverter ON
19- Boost Charge
20- Battery Earth Fault
21- Battery Fault
22- Relay Input 1
23- Relay Input 2

Some UPS functions can be activated with
parameters when an external Normally Open
contact is closed on:
X1-10, 21 / J2-10, 23 or X1-11, 22 / J2- 11, 24

Selectable functions by changing parameters
(password required) are:
0 - No function

1 - Inverter ON

2 - Inverter OFF

3 - Print All

4 - Status Relay

5 - Generator ON

6 - External Bypass ON
7 - External Battery Fuses, or External K3.

See Alarm 4104 - “Battery Fuses”.

24- Relay Output ON

25- Relay Output OFF
26- EPO

(Emergency Power Off)

Voltage free contacts:

Max. DC / AC: 24V / 1.25A
IEC 60950 (SELV circuit)
Min. Signal Level: 5VDC/5mA