Display and keyboard – MJK Automation Shuttle Ultrasonic Level Transmitter and Sensor User Manual

Page 15

Advertising
background image

15

SW 838023

GB Shuttle Manual 100316

Display and keyboard

- the well is empty…

- the well is not empty…

The distance from the sen-
sor to the zero point or the
level read-out must be set
manually - see page

18

.

Note: The dead band
varies for the different
sensor types: 35 cm for
types 200570, 200640 and
200660, and 80 cm for type
200630.

0.00 m

4 mA

20 mA

35 cm from sensor (types 200570,

200640 and 200660)

80 cm from sensor (type 200630)

Shuttle

®

will now indicate the current level in the tank or well

(0 m immediately after initial startup) and is now in service
as a regular level meter, i.e. without the use of the relays and
the analog output for control / alarm.

See the next section for basic settings.

35 cm from sensor

Level read-out = distance
between sensor and bottom
- (minus) the distance be-
tween sensor and surface.

At the same moment Shuttle

®

registers an echo, the zero point is automatically set to the

level that is present in the tank or well.
Furthermore, the mA output is set to 4 mA at the current zero point and 20 mA at a level cor-
responding to a distance of 35 cm from the ultrasonic sensor.

See also Appendix A, Technical Specifications begining on
page

37

.