Mounting – MJK Automation Shuttle Ultrasonic Level Transmitter and Sensor User Manual

Page 8

Advertising
background image

8

GB Shuttle Manual 100316

SW 838023

Mounting

Ultrasonic sensor
Two things are extremely important when
mounting the ultrasonic transmitter: (See
also appendix C!)
1: It should be mounted securely.
2: It should be mounted absolutely vertical.

Use a spirit level in TWO directions.

For the highest accuracy, the ultrasonic
sensor should be mounted as close as
possible to the highest possible level that
can occur + 35 cm (types 200570, 200640
and 200660) or 80 cm (type 200630). See
below:

To ensure a reliable and precise level measurement it

is of vital importance that the ultrasonic sensor points

down absolutely vertical against the liquid surface.

The ultrasonic sensor should be mounted
so the ultrasonic signal has no obstructions
between sensor and surface, i.e. no pipes,
cables, grates etc.

The ultrasonic sensor is equipped with a
nut for bracket mounting. Note the recess
on the nut - it must be fitted safely in the
bracket for firm fixing to the bracket:

We deliver two types of sensor brackets that can be

used in almost any installation. The bracket shown is a

standard universal mounting bracket (200220).

Min. 35 cm (200570,

200640,200660)

Min. 80 cm (200630)

Total distance: Max. + Min.

Highest pos-

sible level

Bottom

Max. measuring range:

200570: 15 m

200640: 12 m

200630: 25 m

200660: 10 m