Appendix

Use the arrow keys to select a new value:

Confirm the new setting:

The actual setting is shown immediately:
(Value in seconds.)

Shuttle

®

is ready for a new selection of a password protect-

ed menu after pressing 'Enter'.
(Re-entering the access code is not necessary if a menu
selection is made within 5 minutes.)

Press 'Escape' if no further password protected menu
selections are needed …

... or confirm with 'Enter' that the changes should be saved,
whereupon Shuttle

®

revert to normal read-out, and the next

password protected menu can be selected.
(Press 'Escape' if the changes should not be saved.)

Investigative measurement intervals
Enter the access code (see page

58

) and press 'D':

Shuttle

®

will normally perform an investigative measurement

every 5 minutes in order to ensure that the unit has not
locked on a false echo - i.e. a level signal which is not the
actual level.
If Shuttle

®

often locks onto solid objects within the normal

interval, the interval for investigative measurements can be
changed in this menu.