Display and keyboard – MJK Automation Shuttle Ultrasonic Level Transmitter and Sensor User Manual

Page 20

Advertising
background image

20

GB Shuttle Manual 100316

SW 838023

Display and keyboard

mA output
When Shuttle

®

is connected to the power supply for the first

time, the mA-output is automatically set to provide 4 mA
at zero level and 20 mA at a level corresponding to 35 cm
below the ultrasonic transmitter.
In this example the range of the mA output is changed from
0 - 1,65 m to 0,5 - 1,5 m. Changes made will not affect the
relay settings.
Note:

Both values can be set over the whole range thus
making it possible to decrease the mA signal at
rising levels and vice versa.

2,00 m

0,00 m

4 mA

20 mA

1,65 m

Shuttle

®

reverts to normal read-out.

2,00 m

0,00 m

4 mA

20 mA

1,50 m

0,50 m