Appendix – MJK Automation Shuttle Ultrasonic Level Transmitter and Sensor User Manual

Page 43

Advertising
background image

43

SW 838023

GB Shuttle Manual 100316

Appendix

C Sensor mounting considerations
General
The ultrasonic sensor is characterized by a
very narrow spread of the ultrasonic signal
(3 ° - 7 ° depending on the type of sensor),
which makes it possible to use the ultrason-
ic sensor under very tight conditions, i.e. in
narrow wells or tanks. 80 % of the ultrasonic
signal is concentrated within this area, which
will give a sufficient echo that is sufficient in
the far most cases.
It is required, though, that the ultrasonic
signal is not being muffled or disturbed by
gratings, pipes, cables etc., and that the
ultrasonic sensor is not mounted so the
ultrasonic signal is sent too close to a tank
wall or well wall.
Signal spread
The illutration to the left shows the spread
of the ultrasonic sensor in conjunction with
the measuring distance, the ultrasonic signal
spread will be 57 cm at a measuring dis-
tance of 9 m. It will appear, that increasing
the measuring distance the distance from
the center line to a smooth wall should be
increased accordingly.

Distance

(m)

at 3°

at 6°

at 7°

1

15

20 22

8

10

11

2

20

31 34

10

15

17

3

26

41 47

13

21

23

4

31

52 59

15

26

29

5

36

62 71

18

31

36

6

41

73 83

21

36

42

7

47

83 96

23

42

48

8

52

94 108

26

47

54

9

57

104 120

29

52

60

10

62 115 132

31

57

66

11

68 125 145

34

63

72

12

73 136 157

36

68

78

13

78 146 169

39

73

85

14

83 157 181

42

78

91

15

89 167 194

44

84

97

Spread-3-6-7.xls

Spread (cm)

Min. dist. from wall (cm)

Figure 1: The signal spread in conjunction with the

measurement distance. The spread value
should be increased by 50 - 100 % if the
surface is not smooth!

Table 1: The ultrasonic signal spread along a smooth

wall and minimum distance to center line in
conjunction to the measuring distance.

NB!

Max. measuring

distance is

31½ ft when us-

ing a standard

sensor bracket !

For greater

distances the

bracket should

be extended

further out over

the well or tank.

Advertising