Appendix – MJK Automation Shuttle Ultrasonic Level Transmitter and Sensor User Manual

Page 48

Advertising
background image

48

GB Shuttle Manual 100316

SW 838023

Appendix

Active measuring range
Shuttle

®

's measuring range is normally set automatically to

a distance corresponding to the ultrasonic sensor's distance

to zero level + 45 cm.
It may become necessary to decrease the active measuring

range so it corresponds to the highest and lowest possible

levels in the well /tank - especially if the ultrasonic sensor is

mounted above a steel grating or an opening in a well cover.

In this example, the Shuttle

®

's active measuring range are

decreased from 0,35 cm - 15 m to 1,45 - 3m measured

from the sensor - that is 3,00 m from the bottom to 10 cm

below the grating or cover.

Shuttle

®

reverts to normal read-out.

0 m

3,00 m

1,45 m

0,35 m

15,00 m

0 m

Normal

measuring

range

Reduced

measuring

range

(1,35 m)

Set the start distance of the measuring range measured
from the ultrasonic sensor (i.e. the highest possible level).

Set the stop distance of the measuring range measured from the
ultrasonic sensor (i.e. the lowest possible level).

Advertising