Appendix – MJK Automation Shuttle Ultrasonic Level Transmitter and Sensor User Manual

Page 49

Advertising
background image

49

SW 838023

GB Shuttle Manual 100316

Appendix

Shuttle

®

reverts to normal read-out.

Response time
When the level changes, the display read-out will change
accordingly with a pre-programmed delay.
The response time is set to 100 mm/sec. from the factory,
which means that an actual level change will not be shown
in the display at a faster rate than 4 in per second.
When measuring on turbulent surfaces, it may become
necessary to increase the response time in order to obtain a
more stable level measurement and also relay function.

Select the desired response time with the arrow keys.
Note:

Changing the response time will also change the
response time for the mA output and the time for
exceeding the set/reset levels.

Advertising