Display and keyboard

Level read-out
The well is not empty
With this function the level read-out can be increased or
decreased on demand. This is almost always required if the
well was not empty during initial startup.
Note:

The learning function settings will be erased and
the relays will be deactivated if the zero point set-
ting is changed.

In this example, the actual level is 80 cm, but Shuttle

®

reads

out 0 m.

2,00 m

0,00 m

0,80 m

Shuttle

®

will now revert to normal level read-out with a

increased read-out value.

If the learning function has been activated, Shuttle

®

will de-

activate the learning function and erase the suspicious levels
that were found last time the learning function was activated.
If the relay outputs are configured for pump control, the
relays will be deactivated, but their limit settings will not be
erased.
Also, delay settings and other settings will not be erased.

1,20 m

- 0,80 m

0,00 m

Select the desired level read-out with the arrow keys.
Shuttle

®

will now read out 0,00 m when the well is empty.