Installation


Electrical data of the terminals

X3/

Resolution 10

bits

Linearity error

±0,5 %

Temperature
error

0,3 % (0 … +60°C)

X3/62

Load capacity

I

max

= 2 mA

Resolution 10

bits

Linearity error

±0,5 %

Temperature
error

0,3 % (0 … +60°C)

Load capacity

I

max

= 2 mA

X3/8

Input resistance Voltage signal: >50 kΩ

Current signal: 250 Ω

X3/9 Load

capacity I

max

= 10 mA

X3/7 Isolated from terminal X3/39 (GND2)

Load capacity

3,3 kΩ

X3/28

HIGH

+12 … +30 V, SPS- level,
HTL

X3/E1

X3/E4

LOW

0 … +3 V, SPS- level,
HTL

X3/39 Isolated from terminal X3/7 (GND1)
X3/A1 Load capacity

For internal supply:
I

max

= 10 mA

For external supply:
I

max

= 50 mA

4.4.6 Final

works

Close frequency inverter

DANGER!

Electrical danger!
The terminal box of the frequency inverter must
be free from

 foreign bodies,
 dirt,
 humidity.

Frequency inverter and cable entries must be
tightly closed so as to make them dustproof
and waterproof. Check for tightness at regular
intervals.

DANGER!

Electrical danger!
Danger of electrical shock when a defective
pump−motor unit is touched!
Have electrical equipment checked regularly by
a qualified electrician.

CAUTION

Improper closing of the frequency inverter
may damage the contacts of the control
terminal module.
Observe the following points to avoid
damages:

 Place the heatsink of the frequency inverter

carefully on the terminal box.

 Place the heatsink upright on the terminal

box from above, do not tilt it!

 When placing the heatsink upon the terminal

box, pay attention to placing the plug at the
heatsink exactly upon the socket connector
at the control terminal module.

 Never force the heatsink upon the terminal

box.

CAUTION

If the cap is plugged on the socket
connector when assembling the frequency
inverter, the control terminal module will be
damaged!

 Remove the cap from the socket connector

at the control terminal module.

 Keep the cap..