Unit of pressure display, Setting the control and data bytes (overview) – Burkert Type 8644 User Manual

Page 111

Advertising
background image

8644/phoenix - 107

S

YSTEM

D

ESCRIPTION

Se-
rial
no.

Setting

Write

Read Con-

trol

byte

Data byte

Explanation

1

Unit of pressure

display on
pressure
module

1

X

0x91

(0) to (2)
[0x00:0x02]

Unit Displayed in bar, kPa or psi

0x00 (0) = bar, 0x01 (1) = kPa, 0x02 (2) = psi

X

0x81

dc

The unit set in the module is read out.

Return value of data byte: 0x00 = bar, 0x01 = kPa, 0x02 = psi

2

Lower threshold

value²

X

0x92

(-10) to (99)
[0xF6:0x63]

Range of values: -10 to 99 (-1 to 9.9 bar)

The lower threshold value must be smaller than the upper threshold
value.

X

0x82

dc

The lower threshold value set in the module is read out.

Return value of data byte: -10 to 99 (-1 to 9.9 bar)

3

Upper threshold

value²

X

0x93

(-9) to (100)
[0xF7:0x64]

Range of values: -9 to 100 (-0.9 to 10 bar)

The upper threshold value must be greater than the lower threshold
value.

X

0x83

dc

The upper threshold value set in the module is read out.

Return value of data byte: -9 to 100 (-0.9 to 10 bar)

4

Reaction time²

X

0x94

(0) to (255)
[0x00:0xFF]

Range of values

Value = 0 threshold treatment deactivated
Value = 1... 255 threshold treatment activated

Reaction time that may be set: 0 ms to 7.62 s (in 30 ms steps)

Calculation reaction time = (value-1) x 30 ms

X

0x84

dc

Feedback value data byte 0 ... 255 - set threshold value (see

above)

5

Sensitivity²
(degree of
smoothing)

X

0x9F

(1) to (100)
[0x01:0x64]

Range of values: 1 to 100

The larger the value, the more strongly the pressure value last

measured is included in the mean value calculation (PT-1-filter), the
higher is the sensitivity and the lower is the degree of smoothing.

Value 100, i.e. the pressure value measured is weighted to 100 %
and the previous measurement to 0 %. In this case the filter is
deactivated.
The sampling frequency of the pressure measurement module is 50

Hz (TA = 20 ms).

X

0x8F

dc

Return value of data byte: 1 to 100

6

Acknowledge

0xAA

dc

Acknowledge telegram is required between different

parametrizations. Instead of this, one can request process data.

1

see Unit of pressure display

² see Threshold values and reaction time
dc: don't care

( ) decimal values in brackets

Unit of pressure display

The pressure value is always sent over the bus in kPa. The pressure unit can only be canged on the local
unit.

Setting the control and data bytes (overview)

Value

sensitivity

1

degree of smoothing