Configuration errors in the station

Type No.

Cause of error

Resolution

3

1

The AirLine terminal is not cleared for
operation in the bus coupler.

Ascertain the precise location of the error
with the aid of the device-specific diagnosis

in your control.
Remove the terminal from the station.

2

The length code of the AirLine terminal
corresponds to a length of 0 byte.

Ascertain the precise location of the error
with the aid of the device-specific diagnosis

in your control.
Inspect the terminal and remove it from

your configuration if necessary.

3

The length code of the AirLine terminal
corresponds to a length of more than 32

bytes.

Ascertain the precise location of the error
with the aid of the device-specific diagnosis

in your control.
Remove the terminal from the station.

4

The station contains a loop 1 module.

Loop 1 modules are not cleared for

operation at the bus coupler.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis

in your control.
Remove the module from the station and
replace it with a loop 2 module.

5

The sum of process data in the local bus is
greater than 250 bytes.

Check the number of process data and

reduce the number of terminals in the

station.

6

More than 64 AirLine terminals and loop 2
modules are plugged in.

Check whether more than 64 AirLine

terminals and loop 2 modules are present

in the station. If yes, reduce the number.

7

The sum of process data for the inputs and
outputs on the PROFIBUS is greater than

176 bytes.

(184 bytes in DPV0 mode)

Remove the terminals from the station.

8

More than eight PCP slaves are plugged
in.

Reduce the number of PCP terminals in

the station.