Warning and error messages – Burkert Type 8644 User Manual

Page 114

Advertising
background image

110 - 8644/phoenix

S

YSTEM

D

ESCRIPTION

Warning and error messages

Warning and error messages (telegrams snet from the pressure module) may be issued as a result of
incorrect parametrization or excursions outside the limits. They contain status bytes specially defined for
the case for the case of errors, whereby status and control byte (previously sent by the master) are not
identical. In some cases, errors are signalled additionally on the local display.

Error

Status byte

Display

Remarks

Parameter value nonvalid

0xE2

none

application error

EEPROM cannot be written

on

0xE3

none

system error

1)

Value above upper limit of

pressure range (10 bar)

0xE4

P o is shown continuously

application error

Value below lower limit of

pressure range (-1 bar)

0xE5

P u is shown continuously

system error

1)

Value above upper
threshold value

0x42

HI and pressure value flash
alternately

warning

Value below lower threshold
value

0x43

LO and pressure value flash
alternately

warning

1)

If system errors occur frequently, a repair may be necessary.