Technical data of the valve block – Burkert Type 8644 User Manual

Page 28

Advertising
background image

24 - 8644/phoenix

S

YSTEM

D

ESCRIPTION

Technical data of the valve block

(using electronic modules and valve types 6524, 6525, 6526, 6527, 0460, 0461)

Profibus

Copper conductor (RS-485), connected via Profibus
connector; Power supply potentialseparated; screen
electrically connected to the functional earth

Recommended cable lengths

see Profibus system data

Interface (Profibus)

No. of connectable AirLINE terminals

Limited by software

max. 64

Limited by power supply unit

max. logic current consumption of connected local bus
module: I

max

2 A DC

Local bus

Mounting dimension

11 mm

16.5mm

Valve operation

C/D (3/2-way)

L/N (5/3-way)

C/D (3/2-way)

L/N (5/3-way)

Type 6524

Type 0460

Type 6526

Type 0461

H (5/2-way)

H (5/2-pulsed)

H (5/2-way)

H (5/2-pulsed)

Type 6525

Type 0460

Type 6527

Type 0461

Flow

300 l/min

200 l/min

700 l/min

500 l/min

Pressure range

2,5 - 7 bar

2,5 - 7 bar

2 - 10 bar

2,5 - 7 bar

(with pressure shut-off)

5 - 7 bar

-

-

-

Power

1 Watt

2 x 1 Watt

1 Watt

/ 2 Watt

2 x 1 Watt

Current (before / after

43/26 mA

38/ - mA

42/33 mA / 96/48 mA

38/ - mA

power reduction)

Valve places (max.)

64

32

32

24

Electrical module

2; 8

2 bistable

2; 4; 3*

2 bistable

Pneumatic module

2; 8

2 bistable

2; 4; 3*

2 bistable

Protection Class in

IP 20

IP 20

IP 20

IP 20

(in terminal model)

Ambient temperature

0 to +55°C

0 to +50°C

0 to +55°C

0 to +50°C

Storage temperature

-20 to +60°C

-20 to +60°C

-20 to +60°C

-20 to +60°C

Nominal operating

Continuous operation (100 % ED)

mode

Operating voltage

24 V / DC; -15 +20 % tolerance**; residual ripple at field bus interface 5 %

Protection Class

3 according to VDE 0580

Total current

Dependent on the connection technology, the expansion stage and the control

ATTENTION!

Observe current consumption of the modules!

On project planning of an AirLINE station, observe the current consumption of the logic of
each participant! This is given in each module-specific data sheet. It may differ from
module to module. Hence the number of possible participants that can be connected
depends on the specific construction of the station.

*3 x 10 mm valves for add-on dimension 16.5 mm
** in the case of the EEx n version, maximum +10 %