Error codes during pcp communication – Burkert Type 8644 User Manual

Page 87

Advertising
background image

8644/phoenix - 83

S

YSTEM

D

ESCRIPTION

Error codes during PCP communication

State conflict

Coding

05h / 01h

Relevance

A start or stop command was sent twice.

Cause

Error only occurs during the start or stop service:

Since start or stop has already been carried out, the service cannot be carried out
again.

Resolution

No action necessary.

Hardware fault

Coding

06h / 02h

Relevance

Access to the object failed due to a hardware fault.

Cause

e.g. no peripheral voltage

Resolution

Remedy the fault.

Object Access Denied

Coding

06h / 03h

Relevance

The object has restricted access rights.

Cause

The object may only be able to be read but is not writable, or it is password protected.

Resolution

Check the access rights in the object description.

Object Attribute Inconsistent

Coding

06h / 05h

Relevance

A service parameter was given with an impermissible value.

Cause

e.g. an incorrect length indication or an impermissible sub-index

Resolution

Check the parameters on the basis of the object description and re-set the service with
the corrected values.

Object Access Unsupported

Coding

06h / 06h

Relevance

The service used cannot be applied to this object.

Cause

e.g. a program sequence can be started or stopped, but not read.

Resolution

Check which services are permitted for this object in the object description.