Threshold values and reaction time – Burkert Type 8644 User Manual

Page 112

Advertising
background image

108 - 8644/phoenix

S

YSTEM

D

ESCRIPTION

Threshold values and reaction time

If the measured value exceeds the upper threshold value (or lies below the lower threshold value), after
expiry of a set reaction time warning messages are sent via the bus (see chapter

Warning and Error Mes-

sages).
At the same time, the pressure value on the local display alternates with the message

HI (upper threshold

value) or

LO (lower threshold value). If the pressure returns to the proper range before expiry of the reaction

time, the watchdog is reset. After the next excursion outside the limits, the reaction time again runs for the
full period before warning messages are issued.

If the reaction time is set to zero, the threshold treatment is deactivated, i.e. the set threshold values are
without effect.

upper threshold value

pressure curve

reaction time t

lower threshold value

10

9

7

8

6

5

4

3

0

2

1

1

5

3

7

9

11

13

17

19

21

15

23

25

27

29

31

33

35

37

41

43

47

45

39

Watchdog activated

Watchdog activated

Watchdog expired

Watchdog activated

Watchdog reset

Watchdog reset

Watchdog expired

Warning messages are

sent to the master and

the pressure value

HI

is

displayed.

Warning messages are

sent to the master and

the pressure value

LO

is

displayed.

→→→→→

→→→→→

→→→→→

→→→→→

Advertising