Terminals, 24 v segment power supply / 24 v main power supply, 24 v segment power supply – Burkert Type 8644 User Manual

Page 38

Advertising
background image

34 - 8644/phoenix

S

YSTEM

D

ESCRIPTION

Terminal configuration of the power supply terminal

ATTENTION!

Earth (ground) the bus terminal!
Earth the bus terminal via one of the FE connections of connector 1.3 or 2.4. For this
purpose, connect the relevant contact to an earthing terminal.

Configuration of the terminal points

Terminals

Left

Right

Colour

Abbrev.

Meaning

1.1

2.1

black

U

S

Segment supply (+24V DC)

1.2

2.2

red

U

M

Main, bus, logic and interface supply (+24V DC)

1.3

2.3

blue

GND

Reference potential

1.4

2.4

---

FE

Functional earth

24 V segment power supply / 24 V main power supply

The reference potential of the segment power supply must be the same as that of the main power supply.
Hence no separate potential structure is possible on the periphery side.

The main power supply and the segment power supply are equipped with elements for protection against
false polarity and transient overvoltage.

24 V segment power supply

You can supply or generate the segment voltage at the bus terminal or one of the supply terminals. There
are several options for providing the segment voltage at the bus terminal:

You can supply the segment voltage at the terminal points 1.1/2.1 and 1.3/2.3 (GND) of the power
supply connector separately.

You can bridge the connections 1.1/2.1 and 1.2/2.2 to assure supply of the segment circuit from the
main circuit.

With a switch between terminal points 1.1/2.1 and 1.2/2.2, you can build up a switched segment circuit
(e.g. also an EMERGENCY OFF circuit).

2.1

2.2

2.3

2.4

1.1

1.2

1.3

1.4

Advertising