Error description – Burkert Type 8644 User Manual

Page 89

Advertising
background image

8644/phoenix - 85

S

YSTEM

D

ESCRIPTION

Error description

Parameter error on the PROFIBUS (SET_PRM-Telegram)

Type No.

Cause of error

Resolution

1

1

An incorrect terminal number is being

used.

Check whether the terminal is
parameterizable.

2

A parameter block is incomplete.

The number of terminals and parameter

blocks does not match.

3

The data length of the parameter block is
too small.

Check the number of parameters.

4

The data length of the parameter block is
too big.

Check the number of parameters.

5

The internal block for configuration,
security value and PCP is too small.

Check the configuration of the parameters

for the terminals.

6

Header byte of the module parameter is
not correct.

Check the first byte of the module
parameters.

7

PCP initialisation of a terminal that has no
PCP functionality.

Check the planning.

8

Too many data blocks for the terminal.

The number of terminals and parameter

blocks does not match.

9

Incomplete data block in a de-activated

terminal.

Check the number of parameters.

Parameter error on the PROFIBUS (CHK_CFG-Telegram)

Type No.

Cause of error

Resolution

2

1

Fewer AirLine terminals were configured

than are present in the station.

Add the terminals in the configuration.

2

More AirLine terminals were configured

than are present in the station.

Delete the superfluous terminals from your

configuration or add the missing terminals
to the station.

3

The first byte of the special ID format of
the AirLine terminal contains errors.

Ascertain the precise location of the error
with the aid of the device-specific diagnosis

in your control.

4

Too few bytes from the special ID format
for the last AirLine terminal configured.

Check the ID format.

5

The sum of configured process data for

inputs and outputs on the station is greater

than 184 bytes (DIP8=OFF) or 176 bytes

(DIP8=ON).

Bring together serveral AirLine terminals in

the configuration so that the process data

become compressed (fewer empty bits).

6

The ID code of the configuration does not

match that of the AirLine terminal.

Ascertain the precise location of the error
with the aid of the device-specific diagnosis

in your control. Check the configuration in

the hardware configurator.

Advertising