8644/phoenix - 31

S

YSTEM

D

ESCRIPTION

Connection technique

Tension spring terminals

Recommended cable lengths

max. 30 m;

cable routing over free areas not permissible

Forwarding

Via potential shunting

Behaviour on voltage drop and

The voltages forwarded from the bus

interruption

terminal to the potential shunters (main and segment
voltage) follow the appliedsupply voltages without delay.

Rated voltage

24 V DC

Tolerance

- 15 % / + 20 % (to EN 61131-2)

Ripple

± 5 %

Permissible range

19.2 V to 30 V

Current loading

Max. 8 A

Technical data of the field bus module Profibus DP bus node

ATTENTION!

Protect 24 V section externally!
This 24 V section must be protected externally with a fuse. The power supply unit must be
capable of supplying 4 times the rated current, so that in case of a fault, blowing of the
fuse is assured.

Minimize heat generation!

For supplying the main voltage and for supplying or tapping the segment voltage, use both
adjacent contacts.

Observe current carrying capacity!

The maximum cumulative current through the potential shunter is 8 A.

Min. current consumption at rated voltage

0.10 A DC

main power supply

(at open circuit, i.e. incoming remote bus attached, no local
bus participants connected, bus inactive)

Max. current consumption at rated voltage

1.25 A DC

main power supply

consisting of:

0.75 A DC for logic supply

0.5 A DC for analog voltage supply

Protective features

Overvoltage

yes

False polarity

yes