English, 4technical data – Burkert Type 8624 User Manual

Page 10

Advertising
background image

8 - 8624-2 Standard

english

4

TECHNICAL DATA

Operating voltage

24 V DC

Power consumption

max. 0,3 W (without proportional valve)

Output current (to valve)

max. 1,0 A

Operating temperature

- 10 ... + 60 °C

Interference resistance

to EN50082-2

Interference emission

to EN50081-2

Inputs

1 setpoint input

4 - 20 mA or 0 - 10 V, adjustable

1 actual value input

4 - 20 mA or 0 - 10 V, adjustable

Resolution for both inputs

10 Bit

Input impedance (4 - 20 mA)

< 200

Input impedance (0 - 10 V)

> 300 k

Output

PWM output

24 V pulse width modulated

Controller

Control algorithm

PI control

Scan time T

A

27 ms

Amplification factor K

P

0 - 10,00

Reset time T

N

0,05 - 200,1 s

Scaling of controlled variable

0,000 - 9999

Housing

Cable outlet

rotatable in 90° steps

System of protection

IP 65

Material

polyamide

Dimensions (W x H x D)

54 x 54 x 61 mm

Order no.

143 570