English, 7 inv - inverted/non-inverted control – Burkert Type 8624 User Manual

Page 35

Advertising
background image

8624-2 Standard - 33

english

Example of an inverted control system

In the following system the actual value at the output of the unregulated pump is to
be controlled by changing the opening of the proportional valve in a return flow
loop. If the actual value is too high (x

d

<0), the correcting variable must be

increased (inverted control).

Fig.: Example of an inverted control system

Î Via this function you set the sense of action between the input signal and

the setpoint of the valve (factory setting: NO).

6.6.7

INV - inverted/non-inverted control

non-inverted control

y = K

p

(x

d

+ T

A

/T

N

x

d

)

inverted control

y = - K

p

(x

d

+ T

A

/T

N

x

d

)

non-inverted control (

NO):

Output signal y of the PI controller
increases with increasing positive
control difference x

d

= w-x.

inverted control (

YES):

Output signal Y of the PI controller
increases with increasing negative
control difference x

d

= w-x.

1

1

Fig.: inverted/non-inverted control

Working

resistance

Pump

Sensor

Proportional valve