English, 6 intg - setting the reset time t – Burkert Type 8624 User Manual
Page 30
Advertising
28 - 8624-2 Standard
english
Î Select the reset time T
N
in a range from 0.05 to 200.1 sec (works setting:
0.50). Higher values result automatically in the display 0.1 and a value
within the range must be entered.
6.6.6
INTG - setting the reset time T
N
increase digit
next digit
2 s
set decimal point
1
The reset time T
N
is the time that is needed to obtain the same magnitude of
change in the controller output with the I fraction as occurs with the P fraction.
Fig.: Setting the reset time T
N