English – Burkert Type 8624 User Manual

Page 13

Advertising
background image

8624-2 Standard - 11

english

M12 (4-pole): Supply voltage and standard signal for setpoint

Configuration:

1

24 V DC output

3

GND

4

Standard signal input, sensor

* wire colours when using standard cables with M8 plug
(3pole)

1

(brown)*

4

(black)

3

(blue)

2

(white)

Configuration

1

24 V DC supply voltage

2

Standard signal input, external setpoint

3

GND

external setpoint

4

GND

supply voltage

* wire colours when using standard cables with M12 plug
(4polig)

M8 (3-pole) Standard signal input, sensor

1

(brown)

4

(black)

3

(blue)*

ATTENTION!

Do not connect a voltage to pin 1 of the 3-pole plug! Pin 1 is a
24 V output to supply the sensor (e.g. 2-conductor
transmitter)

5.3

Connection configuration of flow pressure controller
type 8624-2

Fig.: Connections on flow pressure controller type 8624-2

M12, 4-pole

Supply voltage

and

standard signal input

External setpoint

M8, 3-pole
Standard signal input
Sensor

Advertising