30 - 8624-2 Standard

english

1
T

i

Characteristic and step response of the P fraction of a PI controller

I fraction:

Function:

y =

x

d

dt

T

i

is the integration or floating time. It is the time that expires until the controller

output has run through the entire correcting range.

Characteristics

A purely I controller completely eliminates the effects of disturbances. It thus has a
favourable static behaviour. Because of its finite correcting speed, it works more
slowly than a P controller and tends to oscillation. It is hence dynamically relatively
unfavourable.

Superimposing the P and I fractions:

With a digital controller with sampling time T

A

and noting that T

i

= K

p

/T

N,

one can

write:

y = K

p

(x

d

+ T

A

/T

N

x

d

)

y : controller output
K

p

: amplification factor

x

d

: deviation (x

d

= w - x)

T

A

: sampling time

T

N

: reset time

Characteristic

Step response

control range

∆x

c

correcting range

y

Floating time T

i

y

max

x

d

y

min

x

d

x