English, 3 sens - setting the sensor input – Burkert Type 8624 User Manual

Page 25

Advertising
background image

8624-2 Standard - 23

english

6.6.3

SENS - setting the sensor input

Î Select here whether the sensor is to send 4 - 20 mA or 0 - 10 V to the

controller for the actual value of the controlled variable (factory setting: 0 -
10 V).

Î Next enter the scaling. The range corresponding to the standard signal (4 -

20 mA or 0 - 10 V) is set, i.e. the pressure or flow rate or another type of
controlled variable is entered at 4 mA or 0 V (lower limit) and at 20 mA or 10
V (upper limit).

Settings between 0.000 and 9999 are possible. The unit corresponds to the value
set in the menu item

UNIT.

(factory setting: S LO=0.00; S HI=10.00)

Example:

Lower limit (

S LO) 2,5 bar

4 mA

Upper limit (

S HI) 20 bar

20 mA

=> An actual value signal of 12 mA corresponds in this case to 11.25 bar