7

ERROR MESSAGES

Display

Cause

Remedy

ERR0

Standard signal at transmitter

Check standard signal of trans-

input lies outside range

mitter or its connection to controller

(4 - 20 mA, 0 - 10 V)

ERR1

Standard signal of external

Check standard signal

setpoint lies outside range
(4 - 20 mA, 0 - 10 V)

ERR2

Controller output to proportional

Increase the pressure in order to

valve is > 95%

reach the required setpoint with
the proportional valve selected

ERR9

Only in mode

SENS with

Set the lower limit for the valve drive

S LO

≥ S HI or

correctly value (see 6.6.9.

VALV)

EXLO

≥ EXHI

Set the lower limit for valve drive
correctly (see 6.6.9

VALV)

Actual value too great (can no
longer be compensated) or in
manual mode, the valve
cannot be closed