English – Burkert Type 8624 User Manual

Page 38

Advertising
background image

36 - 8624-2 Standard

english

➔ On using a direct acting proportional valve (Types 6022, 6023, 6024, 6223,

2832, 2834), set the greatest operating pressure expected in the
application (the start of opening is lowered with increasing admission
pressure). With a pilot controlled proportional valve (Type 6223), on the
other hand, set the lowest admission pressure to be expected in operation
(in this case, the start of opening is raised with increasing admission
pressure).

➔ Select the menu item VALV in the configuration mode. The actual value is

displayed.

➔ If at the controller output obtaining no recognizable flow is present, first

increase the pulse-duty factor by pressing the

key until flow is detected.

➔ Now lower the pulse-duty factor by pressing the key until the valve is

just closed, i.e. no flow is present.

➔ Press the

key: the value for start of opening will be stored.

To determine the start of opening of the proportional valve in the current
application, the following steps are executed (on first operation of the device. This
is done immediately after switching on, while the coil is still cold):