G9000 Installation and Operation Manual

The UPS is to be installed in a controlled environment.

Improper storage and installation environment may deteriorate

insulation, shorten component life and cause malfunctions.

Keep the installation environment per standard described as follows:

TABLE 1.1

UPS Installation Environment

No.

Item

Environment standard

1

Installation
location

Indoors

2

Ambient
temperature

Minimum temperature: 32 F(0 C), Maximum temperature: 104 F(40 C) The
average temperature over any 24-hour period must be in the range 41 F (5 C)
to 95 F(35 C).

3

Relative humidity The relative humidity must be held between 5 and 95%. There must be no

condensation due to temperature changes.

4

Altitude

This equipment must not be applied at altitude that exceeds 2250m(7400ft)
above seal level.

5

Dust

Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust should not include iron particles,
oils or fats, or organic materials such as silicone.

6

Inflammable gas

following

IEC654-4

Part 4

There should be no inflammable/explosive gas.

Hydrogen sulfate (H

2

S)

No more than 0.003 PPM

Sulfurous acid gas (SO

2

)

No more than 0.01 PPM

Chlorine gas (Cl

2

)

No more than 0.002 PPM

Ammonia gas (NH

3

)

No more than 1 PPM

Nitrous oxides (NO

x

)

No more than 0.05 PPM

Ozone (O

3

)

No more than 0.002 PPM

WARNING 3

4

!

NOTE