MaxPower Corp Toshiba G9000 Series User Manual

Page 28

Advertising
background image

18

G9000 Installation and Operation Manual

Phase Displacement

1 deg. maximum at 100% load

Inverter Overload

125% for 2 minutes; 150% for 60 seconds

Crest Factor

2.3

Bypass Overload

1000% for 1 cycle

(with bypass available)

Withstand Rating

65,000 A (with optional fuse)

ENVIRONMENTAL

Cooling

Forced Air

Operating

Temperature

32 F to 104 F ( 0 C to 40 C).

Recommended : 68゚F to 86゚F ( 20 C to 30 C)

Relative Humidity

5%

95% Non Condensing

Altitude

0 to 7380 feet No Derating at 40゚C

Location

Indoor (free from corrosive gases and dust)

Paint Color

Munsell N1.5 (Black)

TABLE 1.5.b UPS Efficiencies at Various Loads

UNIT

% Full Load

20%

40%

60%

80%

100%

80 kVA

92.5%

94.3%

95.0%

95.2%

95.8%

100 kVA

92.5%

94.3%

95.0%

95.2%

95.8%

160 kVA

94.7%

95.7%

96.2%

96.5%

96.5%

225 kVA

94.9%

96.2%

96.5%

96.5%

96.5%