Liquid crystal display (8), Menu – MaxPower Corp Toshiba G9000 Series User Manual

Page 32

Advertising
background image

22

G9000 Installation and Operation Manual

2.3

LIQUID CRYSTAL DISPLAY (8)

The Liquid Crystal Display (LCD) touch panel indicates power flow, measured values, operational

guidance, data records and error messages. The LCD panel has a back-light which facilitates viewing

in different ambient lighting conditions. The LCD will automatically clear and turn off, if the screen is not

activated within 3 minute period. The LCD is turned back on when it is touched again. The LCD

ERROR indicator is cleared after 24 hours and can be reproduced by pressing any key on the panel.

2.3.1

Menu

A) MAIN MENU (FIGURE 2.2)

The LCD panel indicates power flow and measured values, while also operating the start/stop

function. The LCD panel also allows the user to verify the status and operation of the UPS Module.

FIGURE 2.2 Main screen

The following will be displayed when the START/STOP key on the MAIN MENU is pressed (Jump

into OPERATION MENU) :

1) Startup/Shutdown Guidance (FIGURE 2.3)

The display indicates the Startup and Shutdown guidance for the UPS system. If this operation is

PIN protected, the user is required to enter the security PIN before the screen can be accessed.

When in remote mode, the message “REMOTE operating model” will appear on this Screen. The

user cannot operate the start and stop functions without changing the setup from remote mode to local

mode.

W

hen bypass voltage is abnormal, the message “Bypass voltage abnormal” will appear.

-Start: When the bypass voltage is abnormal, the LCD asks the operator if an interrupted

transfer is acceptable (Load may be lost).

-Stop: When the bypass voltage is abnormal, the user cannot transfer from inverter to bypass

line.

Advertising