G9000 Installation and Operation Manual

Failure Code List

Table 6.1 Fault Code

Note 3

Note 1

Note 2

Code

indication

Status message

Meaning

Guidance

Buzzer

External

relay

contact

Failure

lamp

UA801

AC INPUT
VOLTAGE OUT OF
RANGE

Input line voltage is out of the specified
range.

CHECK INPUT
POWER
SOURCE

Intermittent

sound

Alarm

AC input

abnormal

UA802

AC INPUT
FREQUENCY OUT
OF RANGE

Input line frequency is out of the specified
range.

CHECK INPUT
POWER
SOURCE

Intermittent

sound

Alarm

AC input

abnormal

UA803

AC INPUT PHASE
ROTATION ERROR

Input line power conductors are not wired
in a proper phase sequence.

CHECK INPUT
POWER
SOURCE

Intermittent

sound

Alarm

AC input

abnormal

UA804

CONVERTER OPE.
PROHIBITED

The converter interlock is active.

Intermittent

sound

Alarm

UA805

INVERTER
OVERLOAD

The output load current has exceeded
105% of the rated current.

WARNING :
DECREASE
LOAD

Intermittent

sound

Alarm

Overload

UA806

INVERTER
OVERLOAD

The output load current has exceeded
110% of the rated current.

WARNING :
DECREASE
LOAD

Intermittent

sound

Alarm

Overload

UA807

INVERTER
OVERLOAD

The output load current has exceeded
125% of the rated current.

WARNING :
DECREASE
LOAD

Intermittent

sound

Alarm

Overload

UA808

INVERTER
OVERLOAD

The output load current has exceeded
150% of the rated current.

WARNING :
DECREASE
LOAD

Intermittent

sound

Alarm

Overload

UA810

INVERTER
OVERLOAD

Short time over-current has been detected
during the inverter operation.

WARNING :
DECREASE
LOAD

Intermittent

sound

Alarm

Overload

UA812

BYPASS VOLTAGE
OUT OF RANGE

Bypass line voltage is out of the specified
range.

CHECK
BYPASS INPUT

Intermittent

sound

Alarm

Bypass input

abnormal

UA813

BYPASS PHASE
ROTATION ERROR

Bypass line power conductors are not
wired in a proper phase sequence.

CHECK
BYPASS INPUT

Intermittent

sound

Alarm

Bypass input

abnormal

UA814

BYPASS
FREQUENCY OUT
OF RANGE

Bypass line frequency is out of the
specified range.

CHECK
BYPASS INPUT

Intermittent

sound

Alarm

Bypass input

abnormal

UA815

TRANSFER
PROHIBITED

Transfer to the bypass is not available due
to bypass abnormality.

Intermittent

sound

Alarm

UA817

EMERGENCY STOP
ACTIVATED

The emergency stop was activated by the
EPO switch or an external contact.

Alarm

UA821

TRANSFER
PROHIBITED

The UPS could not transfer to the bypass
because the inverter output was not
synchronized to the bypass.

Alarm

UA822

TRANSFER
PROHIBITED

The UPS could not transfer to the bypass
because external “generator operation”
signal indicates a backup generator is in
operation.

Alarm