G9000 Installation and Operation Manual

57

Note 3

Note 1

Note 2

Code

indication

Status message

Meaning

Guidance

Buzzer

External

relay

contact

Failure

lamp

UF201

INVERTER
OVERVOLTAGE

Detection of output overvoltage.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF202

INVERTER
UNDERVOLTAGE

Output voltage dropped.below specs.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF203

INVERTER
OVERCURRENT

Detection of inverter overcurrent.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF204

OUTPUT CIRCUIT
ABNORMAL

Detection of a large variation of the
reference error signal (current reference
and actual current).

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF206

UPS CONTROL
CIRCUIT ERROR

Discrepancy between output voltage and
external voltage (bypass, common ac bus)

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF207

ZERO PHASE
OVERCURRENT

Inverter zero-sequence overcurrent.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF208

UPS CONTROL
CIRCUIT ERROR

Cross current is abnormal.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF209

52C ABNORMAL

Error to close the contactor 52C.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF210

52C ABNORMAL

Error to open the contactor 52C.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF211

52C ABNORMAL

No answer from contactor 52C during
inverter operation.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF213

OVERTEMP

Heatsinks temperature exceeds thermal
settings.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF214

COOLING FAN
ABNORMAL

Thermal relay activated protection.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF217

INVERTER
OVERVOLTAGE

Detection of inverter output phase
overvoltage.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF230

ZERO PHASE
OVERCURRENT

Detection of zero-sequence overcurrent.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF253

UPS CONTROL
CIRCUIT ERROR

Discrepancy between output voltage and
inverter voltage, or between output
voltage and bypass voltage.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF256

OUTPUT
VOLTAGE
ABNORMAL

Output voltage is outside of the specified
range.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF257

52C ABNORMAL

Contactor 52C failed to open during load
transfer from inverter to bypass.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF258

LOAD ABNORMAL

Load transfer due to overload for over 4
times within 5 minutes.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF259

ANOTHER UPS
ABNORMAL

No detection of another UPS voltage
signal.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker