MaxPower Corp Toshiba G9000 Series User Manual

Page 65

Advertising
background image

G9000 Installation and Operation Manual

55

Note 3

Note 1

Note 2

Code

indication

Status message

Meaning

Guidance

Buzzer

External

relay

contact

Failure

lamp

UA824

CB2 OPEN

The battery circuit breaker (CB2) is open. TURN ON CB2

Intermittent

sound

Alarm

UA827

52C OPEN
PROHIBITED

The interlock for the inverter output
contactor (52C) is active.

Intermittent

sound

Alarm

UA831

EMERGENCY
BYPASS SWITCH
ON

Emergency bypass switch has been
turned on.

Intermittent

sound

Alarm

UA833

52L OPEN

The load circuit breaker(52L) is turned off.

Intermittent

sound

Alarm

UA834

BATTERY
DEPLETED/AC OUT
STOPPED

The battery voltage has reached the
depleted level.

Major

End-of-

Discharge

Lit on

UA835

TRANSFER
PROHIBITED

The UPS could not transfer to the bypass
because the bypass source has an
abnormality.

Alarm

UA860

REMOTE BUTTON
ABNORMAL

Remote start or stop signal is being
received continuously for a considerable
time.

Intermittent

sound

Alarm

UA861

LOCAL BUTTON
ABNORMAL

Local start or stop signal is being received
continuously for a considerable time.

Intermittent

sound

Alarm

UA870

BALANCER
OVERLOAD

The UPS detected a neutral point voltage
unbalance.

Intermittent

sound

Alarm

Overload

UA890

EXTERNAL ALARM

External Alarm relay turned on.

Intermittent

sound

Alarm

UF001

INPUT CIRCUIT
ABNORMAL

The MMS input reference error signal
exceeds specifications.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF002

CONVERTER
OVERCURRENT

Detection of MMS converter overcurrent.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF003

CONVERTER
ABNORMAL

Pre-charging circuit is not working
properly.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF011

CB1 ABNORMAL

Major discrepancy between reference
signal and actual state of contactor CB1.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF052

CB1 ABNORMAL

Minor discrepancy between reference
signal and actual state of contactor CB1.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF056

CONVERTER
OVERCURRENT

Detection of SMS converter overcurrent.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF059

INPUT CIRCUIT
ABNORMAL

The SMS input reference error signal
exceeds specifications.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF102

DC OVERVOLTAGE

DC voltage surpasses the overvoltage
level.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF103

DC
UNDERVOLTAGE

DC voltage dropped below the
undervoltage level.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF108

CHOPPER
OVERCURRENT

Detection of DC overcurrent from backup
battery.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

Advertising