Terminal, Ups cabinet, External to ups – MaxPower Corp Toshiba G9000 Series User Manual

Page 40: Cabinet, Relay, Coil, Nec class 2, Power source, Contact

Advertising
background image

30

G9000 Installation and Operation Manual

A) Output Contacts (for external alarm annunciation)

Output contacts consist of form “A” dry type contacts. Rated capacity of all output contacts is NEC

Class2 (30Vdc/1Adc). All dry contacts should be operated at their rated values or lower. Figure 2.11

illustrates a typical installation. The external relay can also be a lamp, LED, computer, etc.

FIGURE 2.11 Control Wiring for External Contacts

Terminal

UPS Cabinet

External to UPS

Cabinet

Relay

Coil

NEC Class 2

Power Source

Relay

Contact

Terminal

Details of output alarm contacts : TN1

Terminals 1 to 2 "Summary Alarm" contact

Activated when a major fault has occurred with the system.

Terminals 3 to 4 "Load on Bypass" contact (OUT1)

Activated when the power is supplied from the static bypass input.

Terminals 5 to 6 "Load on Inverter" contact (OUT2)

Activated when the power is supplied by the inverter.

Terminals 7 to 8 "Battery Operation" contact (OUT3)

Activated when the battery is operating following an AC power failure.

Terminals 9 to 10 "Converter Operation" contact (OUT4)

Activated when the converter is operating.

Terminals 11 to 12 "Battery Low Voltage" contact (OUT5)

Activated when the battery voltage drops below discharge end voltage level during inverter

operation (i.e. During AC fail condition).

Terminals 13 to 14 "Overload" contact (OUT6)

Activated when an overload has occurred to the system.

Terminals 15 to 16 "Total Alarm" contact (OUT7)

Activated during major fault, minor fault and alarm events.

Terminals 17 to 18 "Spare" contact (OUT8)

Terminals 19 to 20 "52C Close" contact (OUT9)

Activated when the inverter output contactor 52C has closed.

User supplied

Advertising