Operation overview – MaxPower Corp Toshiba G9000 Series User Manual

Page 18

Advertising
background image

8

G9000 Installation and Operation Manual

1.4

OPERATION OVERVIEW

The UPS provides two power paths between the utility source and the critical load.

Figure 1.1 shows the path for normal operation, with the load powered by the inverter.

Figure 1.2 shows the path for bypass operation, with the load supplied through the static

bypass line.

A) Normal operation: Load power supplied by each system UPS inverter.

FIGURE 1.1 Single Line Diagram - Normal Operation: Load powered by UPS inverter

During normal operation, the path through the UPS inverter is used to power the load.

In Figure 1.1 input AC power is converted to DC by the Converter. DC power is utilized to charge

the UPS battery and to provide power to the Inverter. The Inverter converts the DC power to clean AC

power to supply the critical load.

The conversion - inversion process eliminates any voltage transients or fluctuations existing in the

input power before it reaches the critical load.

The power drawn by the critical load is equally shared between all UPS systems when multiple

UPSs are in Parallel Operation. (Refer to Figure 3.4 that shows a sample of Parallel Operation System

Configuration.)

UPS Module

Power Flow

Not in Use

AC input

CB

CB3

CONVERTER

/ CHARGER

INVERTER

Output

52C

CB1

External

BATTERY

User Supplied

MCCB

Static Transfer

Switch

52S

CB2

Battery Cabinet

Bypass

input

CB

User supplied

MCCB

Advertising