MaxPower Corp Toshiba G9000 Series User Manual

Page 69

Advertising
background image

G9000 Installation and Operation Manual

59

Note 3

Note 1

Note 2

Code

indication

Status message

Meaning

Guidance

Buzzer

External

relay

contact

Failure

lamp

UF401

52S ABNORMAL

Error to close the contactor 52S.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF402

52S ABNORMAL

Error to open the contactor 52S.

CALL SERVICE
ENGINEER

Continuous

sound

Major

Lit on

UF420

52L OPERATION
ERROR

Load circuit breaker 52L opened during
inverter operation.

CHECK 52L

Continuous

sound

Major

Lit on

UF451

52S ABNORMAL

Contactor 52S failed during load transfer
from inverter to bypass.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

UF452

CB3 ABNORMAL

Contactor CB3 is not working properly.

CALL SERVICE
ENGINEER

Intermittent

sound

Minor

Flicker

(Note 1) 1) "Major" is defined as major failure. Inverter transferred to the static bypass line;

2) "Minor" is defined as a minor failure. UPS continues to operate normally, but cause of

alarm must be identified;

(Note 2) Indicates one of two possible LED illumination patterns - continuously on (lit) or intermittent

(flicker).

(Note 3) Code indication means:

UA+++ ----------------------- Alarm

UF+++ ----------------------- Failure

U%0++ ----------------------- Rectifier circuit failure

U%1++ ----------------------- DC circuit failure

U%2++ ----------------------- Inverter circuit failure

U%3++ ----------------------- Control circuit failure

U%4++ ----------------------- Bypass system failure

U%8++ ----------------------- Alarm

U%+00 - U%+49 --------- Major failure

U%+50 - U%+99 --------- Minor failure

*)

“+” denotes any numeral from 0 to 9

*)

“%” denotes either “A” or “F”

Advertising