MaxPower Corp Toshiba G9000 Series User Manual

Page 52

Advertising
background image

42

G9000 Installation and Operation Manual

TABLE 3.5 Crimp Type Compression Lug

WIRE

SIZE

WIRE

STRAND

RECOMMENDATION

CRIMP TOOL REQUIRED
BURNDY TYPE Y35 OR Y46

(CODE)

CLASS

VENDOR

CAT. NO.

COLOR KEY

DIE INDEX

1

B

I

BURNDY

ILSCO

BURNDY

YA1C

CRA-1L

YA25-LB

GREEN
GREEN

---

11 / 375
11 / 375

1019

1/0

B

I

BURNDY

ILSCO

BURNDY

YA25

CRA-1/OL

YA25-LB

PINK
PINK

---

12 / 348
12 / 348

1020

2/0

B

I

BURNDY

ILSCO

BURNDY

YA26

CRA-2/OL

YA27-LB

BLACK
BLACK

---

13
13

1021

3/0

B

I

BURNDY

ILSCO

BURNDY

YA27

CRB-3/OL

YA28-LB

ORANGE
ORANGE

---

14 / 101
14 / 101

1022

4/0

B

I

BURNDY

ILSCO

BURNDY

YA28

CRB-4/OL

YA29-LB

PURPLE
PURPLE

---

15
15

1023

250 MCM

B

I

BURNDY

ILSCO

BURNDY

YA29

CRA-250L

YA30-LB

YELLOW
YELLOW

---

16
16

1024

300 MCM

B

I

BURNDY

ILSCO

BURNDY

YA30

CRA-300L

YA32-LB

WHITE
WHITE

---

17 / 298
17 / 298

1026

350 MCM

B

I

BURNDY

ILSCO

BURNDY

YA31

CRA-350L

YA34-LB

RED
RED

---

18 / 324
18 / 324

1027

400 MCM

B

I

BURNDY

ILSCO

BURNDY

YA32

CRA-400L

YA36-LB

BLUE
BLUE

---

19 / 470
19 / 470

1027

500 MCM

B

I

BURNDY

ILSCO

BURNDY

YA34

CRA-500L

YA38-LB

BROWN
BROWN

---

20 / 299
20 / 299

1029

NOTE: When using crimp type lugs, the lugs should be crimped to the specifications given in the

manufacturer's instructions for both crimp tool and lug.

FIGURE 3.1 UPS Terminal Designation

AC input

CB3

CONVERTER

/ CHARGER

INVERTER

Output

52C

CB1

External
BATTERY

Static Bypass

Transfer Switch

52S

CB2

Bypass

input

Terminals

A40
B40
C40

Terminals

A
B
C

Terminals

A50
B50
C50

Terminals

BP
BN

Advertising