Gas Requirements

IMPORTANT: Any product revisions or conversions
must be made by the Manufacturer’s Authorized
Dealers, Distributors or local service personnel.

IMPORTANT: The tumbler must be isolated from
the gas supply piping system by closing its
individual manual shut-off valve during any
pressure testing of the gas supply piping system at
test pressure equal to or less than 0.5 psig
(3.45 kPa, 34.5 mbar).

IMPORTANT: The tumbler and its manually
operated appliance gas valve must be disconnected
from the gas supply piping system during any
pressure testing of that system at test pressures in
excess of 0.5 psi (3.45 kPa, 34.5 mbar).

IMPORTANT: The installation must comply with
local codes or, in the absence of local codes:

with the latest edition of the “National Fuel

Gas Code,” ANSI Z223.1/NFPA 54 in the
U.S.A.,

with CSA-B149.1 or Natural Gas and Propane

Installation Code in Canada,

and Australian Gas Association/Australian

L.P. Gas Association requirements in
Australia.

Obtain specific gas service pipe size from the gas
supplier. Refer to Table 6 for general pipe size.

The following must be furnished and installed by the
customer for the gas service line to each tumbler.
Refer to Figure 12.

Sediment traps

Shut-off valves

Supply pressure taps

It is important that equal pressure be maintained at all
tumbler gas connections. This can best be done by
installing a one inch (25 mm) pipe gas loop. Refer to
Figure 13.

NATURAL GAS line pressure must be maintained at
6.5 water column inches (1.62 kPa) with no less than 5
water column inches (1.24 kPa) and no more than 10.5
water column inches (2.61 kPa), with all gas
appliances running (tumblers, water heaters, space
heaters, furnace, etc.). An in-line pressure regulator
may be required if the line pressure exceeds 8 water
column inches (2.0 kPa) with all gas appliances
running.

LIQUID PETROLEUM GAS (L.P.) line pressure must
be maintained at 11 water column inches (2.74 kPa),
with no less than 10 water column inches (2.49 kPa)
and no more than 13 water column inches (3.23 kPa),
with all gas appliances running (tumblers, water
heaters, space heaters, furnace, etc.).

For converting Non-CE models from Natural Gas to
L. P. Gas:

T30 – M4707P3

T45 – M4880P3

CE GASES refers to Installing CE Gas Drying
Tumblers
sections, the above data does not apply to
the CE.

WARNING

To reduce the risk of fire or explosion, DO
NOT CONNECT THE GAS LINE TO THE
TUMBLER IF THE GAS SERVICE IS NOT
THE SAME AS THAT SPECIFIED ON THE
TUMBLER SERIAL PLATE! It will first be
necessary to convert the gas burner
orifice and gas valve. Appropriate
conversion kits are available.

W060

WARNING

To reduce the risk of fire or explosion, if
the tumbler is to be connected to
Liquefied Petroleum (L.P.) gas, a vent to
the outdoors must be provided in the
room where the tumbler is installed.

W062