Installing steam trap and making condensate, Return connections, Warning – Alliance Laundry Systems Drying Cabinet User Manual

Page 46

Advertising
background image

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Steam Requirements

70304601

44

Installing Steam Trap and Making
Condensate Return Connections

The steam trap must be installed and the coil outlet
connections must be connected to the condensate
return lines. The following steps outline the procedure
for installing the steam trap and connecting the
condensate return lines. Refer to Figure 14 for typical
installations.

1. Use flexible lines between steam inlet solenoid

and steam coils, as well as outlet between steam
coil and traps.

2. If necessary, install a strainer at the end of each

flexible hose.

3. Install a steam trap to each strainer.

IMPORTANT: Steam trap must be installed a
minimum of 18 inches (457 mm) below the steam
coil outlet connections.

4. Install a shut-off valve to each steam trap.

5. Connect to the condensate return lines.

6. For steam solenoid valve wiring connections,

refer to Wiring Diagram supplied with tumbler.

WARNING

The flexible steam hoses connecting the
coil outlet connections and steam traps
must have a minimum of 125 psig
(pounds per square inch gauge) (8.79 kg/
sq. cm.) working pressure. A shut-off
valve must be installed downstream from
each steam trap so the condensate return
line can be isolated in event a steam trap
requires maintenance.

Each steam trap must be supported so
minimum load is exerted on the coil outlet
connection.

W066

Advertising