Electrical Requirements

70304601

42

Electrical Requirements for Electric
Models

Refer to Table 11.

NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code for 75°C Conductors and
are intended for use as a guideline only. Electrical
connections should be made only by a qualified
electrical contractor in accordance with all
applicable local and national requirements.

NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.

NOTE: Connect to individual branch circuit.

NOTE: 3 Phase Only – Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).

For 21 kW T30 Electric Models:

Table 11

Serial Plate

Voltage

Terminal Block

Connections

Required

Current

(Amps)

Recommended
Breaker Rating

(Amps)

Breaker

Poles

Recommended

Minimum

Conductor Size

[AWG (mm

2

)]

200-208V/60Hz/3ph*

L1, L2, L3,

and ground

62**

80

3

4 (21.2)

200V/50Hz/3ph*

L1, L2, L3,

and ground

60**

80

3

4 (21.2)

230-240V/50Hz/3ph*

L1, L2, L3,

and ground

55**

70

3

4 (21.2)

240V/60Hz/3ph*

L1, L2, L3,

and ground

54**

70

3

4 (21.2)

380V/50 or 60Hz/3ph*

L1, L2, L3,

and ground

33**

45

3

8 (8.37)

400-415V/50Hz/3ph*

L1, L2, L3,

and ground

31**

40

3

8 (8.37)

460-480V/60Hz/3ph*

L1, L2, L3,

and ground

27**

35

3

8 (8.37)

*

These serial plate voltages are only options available on the T30 electric models. Current (Amp) is for one pocket only.

** Per heater on T30 electric models, each has two heaters.