Electrical Requirements

70304601

40

Electrical Requirements for Gas and
Steam Models

Refer to Table 9 and Table 10.

NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code for 75°C Conductors and
are intended for use as a guideline only. Electrical
connections should be made only by a qualified
electrical contractor in accordance with all
applicable local and national requirements.

For T30 Gas and Steam Models
(For Total Machine):

NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.

NOTE: Use copper conductors only.

NOTE: 3 Phase Only – Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).

Table 9

Serial Plate

Voltage

Terminal Block

Connections

Required

Current

(Amps)

Recommended

Fuse or

Breaker Rating

(Amps)

Breaker

Poles

Recommended

Minimum

Conductor Size

[AWG (mm

2

)]

120V/60 Hz/1ph

L1, Neutral,

and ground

16.0

20

1

12 (3.31)

208-240V/60Hz/

1ph

L1, L2, Neutral,

and ground

8.0

10

2

14 (2.08)

100V/60Hz/1ph

L1, Neutral,

and ground

22.0

30

1

10 (5.26)

200-220V/60Hz/

1ph

L1, Neutral,

and ground

11.6

15

1

14 (2.08)

100V/50Hz/1ph

L1, Neutral,

and ground

24.2

35

1

8 (8.37)

200V/50Hz/1ph

L1, Neutral,

and ground

15.0

20

1

12 (3.31)

230-240V/50Hz/

1ph

L1, Neutral,

and ground

15.0

20

1

12 (3.31)

200-208V/60Hz/

3ph

L1, L2, L3,

and ground

6.4

10*

3

14 (2.08)

240V/60Hz/3ph

L1, L2, L3,

and ground

6.4

10*

3

14 (2.08)

200V/50Hz/3ph

L1, L2, L3,

and ground

5.8

10*

3

14 (2.08)

230-240V/50Hz/

3ph

L1, L2, L3,

and ground

7.0

10*

3

14 (2.08)

380V/50 or 60Hz/

3ph

L1, L2, L3,

and ground

3.0

10*

3

14 (2.08)

400-415V/50Hz/

3ph

L1, L2, L3,

and ground

3.2

10*

3

14 (2.08)

460-480V/60Hz/

3ph

L1, L2, L3,

and ground

3.3

10*

3

14 (2.08)

*

3 Phase machines should not have fuses, breakers only.