Error and Flags


E-Mon Energy User Manual

15-3

E-MON

What Is a Flag Status?

The Flag Status is the condition of a meter within E-Mon Energy™. With most of our meters (IDRs) we provide

several features that are actually built into the meter, like the tamper alarm. With E-Mon Energy, we can view a

problem or an error by simply accessing the group and viewing the hardware. The Flag Status function is accessible

through the Access Location window, under the Read Hardware function. From this view a user can access the

condition of a meter by clicking on the Flag Status button. These flag errors are usually displayed in red and range

from power failure, load, tamper, and the current state of the meter. The illustration below shows a Power Failure.

Figure 14.6 - Access Group Flag Status

Panel Group/Field

Description

Flag Status

This button allows you to access the meter’s current condition regarding

flags.

Status

This field displays the condition of the Meter. If the condition states

“<Bad>, there is no connection and there may be a serious problem. If

the condition is <ok>, then communication is enabled with the meter.

Power Failure Status

This field will display any power failures at any point with the meter. If

the voltage drops past the required power factor threshold a flag will

display how many times it has occurred (i.e. >15), the last time it

occurred by date (i.e. 12/30), and the last reading recorded (i.e. 15.44).

When no power failures exist, the field will display <none>.

Tamper Alarm

This field will display an active <on> flag when a door is open on the

meter. If the Tamper Alarm is not on, the column will display <off>.

O’Load (Over Load)

This field will display an Overload flag when the meter has excessive

amperage (i.e. 200 amps through the sensors on a 100 amp meter).

When no problems exist, the field displays <none>.

Power

This field will display any general power/voltage errors with the meter

(i.e. low, noisy or unstable). Low = voltage drop below nominal level,

noisy = dirty power supply, harmonics, unstable = fluctuating levels.

When no problems exist, the field displays <normal>.

MTR Reg

This field will display any malfunctions with the internal meters real-

time clock (i.e. <Bad>). When no problems exist, the field displays

<ok>.

IDR State

This field will display any problems that may exist with the

functionality of the IDR. When no problems exist the field displays

<ok>.